Air conditioning and ventilation in a restaurant: why the cool air escapes

Why the air conditioning in a venue doesn't cool even though it runs flat out. How kitchen extraction relates to cooling the dining room, and what can be solved at the design stage.

A typical summer phone call: the air conditioning has been running flat out since morning, the electricity bill is high and the kitchen is still unbearable. The first thought is usually that the unit is too weak. In most cases it isn't — the cooled air simply doesn't stay in the venue.

Where the cool air goes

The extraction above the cooking line removes thousands of cubic metres of air an hour. Physics is relentless: the same volume has to get back into the venue. If there's no controlled supply, air is drawn from wherever it can — under the doors, through gaps and, above all, from the dining room. That is, exactly the air the air conditioning has just cooled.

In practice this means the air conditioning in the dining room is cooling the kitchen. And the kitchen sends that cool air out through the hood onto the street. The owner pays for the unit, the electricity and for cooling the outdoors — and nobody in the venue gets anything out of it.

Why a stronger air conditioner won't help

It's the same mistake as replacing a fan with a more powerful one when the extraction doesn't draw. Adding power doesn't fix the cause; it only raises consumption. If the air is escaping, it will keep escaping even when cooled to a lower temperature — just more expensively.

The solution: cool the air that comes in

We bring into the venue the same amount of air that the extraction removes. This supply passes through a unit with a cooling section, so the air comes in already cooled. The air conditioning in the dining room then isn't chasing a loss — it just tops up the cooling for the room and the guests.

You can see the difference in consumption too. A unit that isn't working against a constant stream of hot outdoor air runs less and wears less.

A cassette unit next to the hood

The second common mistake is positioning. A cassette air conditioner blows along the ceiling in four directions. When it's near the hood, its airflow breaks up the capture zone above the cooking line. Instead of going into the extraction, steam and smells scatter around the kitchen. The extraction is running at full power and nobody understands why it doesn't draw.

That's why the position of air-conditioning units is decided together with the extraction route, not afterwards. When one company installs the air conditioning and another the ventilation, usually neither thinks about this detail.

What else is worth thinking through in advance

  • The heat load is calculated from the appliances, lighting and number of guests — not from the floor area.
  • Condensate drainage must be accessible, otherwise the ceiling gets taken apart at every service.
  • Unit noise in the dining room: a guest sits under it all evening.
  • In a food-service venue air-conditioner filters clog with grease faster than in an office.
  • In winter the supply air has to be heated, or a cold stream blows onto the tables by the wall.

When it's cheapest to deal with

At the design stage. Ventilation ducts and refrigerant pipes can be routed so they don't get in each other's way while the walls are bare. Rerouting finished pipework in a finished interior costs many times more than the same thing done in the right order.