26/08/2026 · 3 min read
Is your hood dripping? Why condensation forms and how to get rid of it
Condensate from the hood falls onto the cooking line and into food. Why it happens and which solutions work.
A dripping hood is not just a nuisance. A drop that falls into hot oil or onto a finished plate is a hygiene problem, and with a fryer a safety one too.
The cause is always the same: steam condenses before the system manages to remove it. There are several reasons why this happens.
Why condensate forms
Water vapour from cooking rises. When it hits a colder surface, it turns back into water. In a hood this happens on the canopy sheet metal, on the filters and in the duct.
A small amount of condensate forms in every kitchen and that is expected. The problem starts when there is so much of it that it runs off.
The most common causes
Weak extraction
If the system doesn't remove enough air, steam collects under the canopy and has time to condense. This is the most common reason, and it also means you have other problems you may not have noticed yet.
Clogged filters
A greasy filter holds the steam underneath it. Condensate also collects on it and runs off the edge.
Cold ductwork
If the duct passes through an unheated space or runs along an outside wall, steam condenses inside it. The water then runs back towards the hood.
This problem is much worse in winter, and owners often blame the weather rather than the system.
No fall in the duct
A horizontal duct without a slight slope has no way to drain condensed water. A correctly routed duct falls towards a drain point.
No gutter and drain in the canopy
A good commercial canopy has a gutter around its perimeter that catches and drains condensate. Cheaper versions don't have one, or it has the wrong fall.
What to do about it
| Cause | Solution | Effort |
|---|---|---|
| Weak extraction | Fix make-up air, recalculate capacity | Medium |
| Clogged filters | Clean or replace | Low |
| Cold ductwork | Insulate the route | Low to medium |
| No fall | Adjust the duct routing | Medium |
| No gutter in the canopy | Add one or replace the canopy | Medium |
What wiping won't solve
Kitchens often get used to it and wipe the condensate regularly. The problem is that water running down the canopy carries grease with it. That ends up on the cooking line and on the floor, creating a slippery surface.
Condensate in the duct also speeds up corrosion and fouling.
Questions and answers
Is a dripping hood a hygiene problem?
Yes. Condensate from a commercial hood contains grease and dirt from cooking. It must not drip onto surfaces where food is prepared.
Why does it only drip in winter?
Most likely you have uninsulated ductwork running through a cold space. In summer the temperature difference is smaller and less condensate forms.
Can it be solved without replacing the hood?
In most cases, yes. Replacing the canopy is the last option, not the first.
When can you come for a site visit?
Within a working week.
Related: restaurant hoods · kitchen extraction · mould and damp in a commercial kitchen.
Solve condensation in your kitchen