People usually call us after they have already paid once. The system is installed, the invoice is settled, and yet there is smoke under the ceiling and the cooks run outside after four hours to catch their breath. The previous contractor either doesn't pick up the phone or insists everything works as specified.

The whole project is in our references.
We visit kitchens like this often. The good news is that in most cases there is no need to tear out the whole system.
What we find most often
Air is extracted but has nothing to replace it. The most common fault in Slovakia. Someone installed a powerful hood and solved make-up air with a half-open window. The fan runs at full speed, but the air has nowhere to come from. The kitchen goes into negative pressure, doors are hard to open, gas appliances burn worse and extraction reaches a fraction of the rated value.
Undersized ductwork. The fan can do 4,000 m³/h, the duct lets through half of it. The rest turns into noise and electricity consumption.
Far too many bends. Every bend in the duct costs pressure. We have seen runs with seven changes of direction because someone didn't want to cut through a load-bearing wall.
Fan located inside the kitchen. Noise right above the cooks' heads. The staff then switch the extraction off so they can work, and the owner can't understand why the dining room smells of the fryer.
Missing access doors. The duct can't be cleaned. Grease builds up for years until it becomes a fire hazard.
Hood at the wrong height or size. The canopy must overhang the edge of the appliance. When someone shortened it to fit a suspended ceiling, the steam escapes at the sides.
How the diagnosis works
The site visit takes about an hour and a half. We do the following:
- 1. We measure the actual airflow on both extract and supply. Not the rated value, but what the system really delivers.
- 2. We check the pressure relationship between the kitchen and the dining room. Air should flow from the dining room into the kitchen, not the other way round.
- 3. We walk the duct route and work out where pressure is lost.
- 4. We look inside the duct if possible. The grease layer tells how long it hasn't been cleaned.
- 5. We calculate the load from the appliances. We often find that the kitchen has since added a fryer or a grill while the system was sized for the original equipment.
That tells us what can be kept.
What can be saved and what can't
| Problem found | Solution | Effort |
|---|---|---|
| No make-up air | Add a supply air unit | Medium, the system stays |
| Undersized duct on part of the route | Replace the section | Medium |
| Noisy fan in the kitchen | Move it outside, add silencers | Medium |
| Missing access doors | Add them to the existing duct | Low |
| Clogged duct | Clean it | Low |
| Badly positioned hood | Modify or replace the canopy | Low to medium |
| Whole system sized for a different kitchen | Replace the assembly | High |
The last row is rare. Usually it is a combination of the first five, and those can be fixed step by step without closing the business.
What it costs compared with a new installation
A refurbishment usually comes out cheaper, because the ductwork, hangers and penetrations through the structure already exist. Those are the items that make up a large part of the price of a new installation. We give an exact figure only after the site visit, but experience says a repair costs a fraction of the original investment.
It makes no sense to repair a system that was designed for half the kitchen from the start. In that case we say so straight away.
What to prepare before our visit
- the original documentation or quote from the previous contractor, if you have it
- a list of appliances including their power input
- information about what has changed in the kitchen since installation
- whether and when the system was cleaned
If you have none of this, we will do the visit anyway. We'll measure it ourselves.
Questions and answers
Do I have to close the business for the refurbishment?
In most cases, no. The work can be split up and done outside opening hours.
Will you take on the warranty for parts installed by someone else?
We cannot vouch for the original parts. We vouch for what we install and for the measured result after completion.
How quickly can you come?
Within a working week.
Do you prepare design documentation?
No. We do calculations and engineering, i.e. the capacity calculation, duct sizing and the equipment layout. We do not produce design documentation in the sense of the Building Act.